Page 15 - 國郁企業股份有限公司 | KUOYUH W.L.Enterprise Co.,Ltd
P. 15

R

             88A Series Thermal Circuit Breaker

             Single Pole Push to Reset


             •Technical data
             •Current rating range  3~16A
             •Input voltage rating  125/250VAC; 50VDC
             •Interrupting Capacity  125/250VAC x 1,000A(UL 1077)
              •Typical life   1,000 operations at 200% overload.
             •Insulation co-ordination  Rated impulse withstand voltage 2.5kV
              •Dielectric Strength  > 1,500VAC/min.
             •Insulation Resistance  >100MOHM (DC 500V)
             •Degree of protection  Terminal area IP00,  operating area IP40
             •Mechanical/Environmental Data
             •Operating Ambient Temperature: -10  to +60℃  ℃
             •Termination: 250’’(6.35mm)quick connects or solder terminals
              •Mounting: Various options. See Ordering Information and drawings
                                                                                KUOYUH
              •Panel Cutout:                                                   88A Series
                                                                                XX Amp
                                                                                 S
                                                                                 AC125/AC250V
                                                                                .  50/60Hz
                                                                                T . VU ..
                                                                                SUD
                                                                                  125/250Vac
                                                                                  DC32V
                                                                               C  US 50/60Hz
                                                                                 TC1,OL0,C1 1KA
             •Compliance with Rohs                                             Line  Load
              The product accords with the requirement of ROHS( 2011/65/EU)
              Contacts use Exempted item of RoHS Directive 2010/571/EU 8(a)
             •Compliance with REACH, PAHS, PH1, PH2, PH3
             •Typical applications                                 •88A Series 3A~16A Trip Time Curves
               Tarnsforms, Motors, Battery chargers, Power supplies,
                                                                     1000%
               appliances, extra low voltage systems, machinery.     800%
                                                                                                       TRIP TIME
             •Calibration(at25 )℃                                    600%                         OVERLOAD  0.34-1.05sec
                                                                                                   600%
              •100% of Rated Current:      Hold , No Trip                                          500%  0.42-1.75sec
                                                                                                       0.62-3.05sec
                                                                                                   400%
              •135% of Rated Current:      Trip Within 1 Hour.       500%                          300%  1.50-5.5sec
                                                                                                   200%
                                                                                                       5.2-30.0sec
                                                                                                       Trip in 1Hour
                                                                                                   135%
              •200% of Rated Current:     5.2- 30.0 sec Trip                                       100%  Hold,No Trip
              •300% of Rated Current:     1.5-5.5 sec Trip          Load Current AS Percent of Circuit Breaker Rating  400%
             •Approval                                               300%
             •Approval & File No.       Rated current     Rated voltage
             •CUL UL E155159      3-16A    125/250VAC; 50VDC         200%
             •TUV SUD B150158611006  3-16A  125/250VAC               135%
             •CCC                 3-16A    125/250VAC                100%
             •VDE                 3-16A    125/250VAC                  0.1     1.0    TIME IN SECONDS  100  1000  10000
                                                                                       10
                                                                                 TRIP CURVES ARE SPECIFIED OF 25°C/77°F
        Order Guide                                                  •Ambient Temperature Correction Factor
           88A - 0 5         -  B      A      0       N               Ambient  -10°C  0°C  10°C  25°C  35°C  40°C  50°C  60°C
                                                                      temperature
                                                                      Multiplication
                                                                      factor   *1.30  *1.20  *1.10  1.00  *0.94  *0.85  *0.73  *0.68
            Series    Amp rating  Color Button  Nut  Waterproof  Terminal Finish  The time/current characteristic curve depends on the ambient temperature prevailing. In order to
             係列號      額定電流     按鍵顏色    螺母    防水帽     端子電鍍             eliminate nuisance tripping. Please multiply the circuit  breaker current ratings by the derating
                                                                      factor shown below.
                                                                                           Example : Normal Continuous Current = 10A
                                                                                                Ambient Temperature = 45°C
                                                                                                Multiplication Factor =  0.85
                                                                     •Internal connection diagram  Recommended Rating= 10A/0.85=11.8A
            03= 3A   B = Black  0  None  0  None    S =plate with Tin
            04= 4A                                                                   Load
            05= 5A  W= White  A          R          N =plate with Nickel
             •
             •       R= Red
             •
             •
            13=13A
            15=15A            B
            16=16A                                                                  Line
      * The specification subject to change without notice. The drawing is for reference only.
      KUOYUH  W.L. Enterprise Co.,Ltd.
                      KUOYUH  W.L. Enterprise Co.,Ltd.
      No.17 Kejia 6th Road Douliu City YunLin Hsien 64057  Taiwan R.O.C
      http//www.kuoyuh.com.tw     sales@kuoyuh.com                                                    國郁企業股份有限公司
                                                                                                      64057 雲林縣斗六市科加六路17號
      Taiwan Tel: 886 5 551 3222  Fax: 886 5 551 3030
      China Tel: 86 769 8366 6388  Fax: 86 769 8366 6362
      Issue:A0                                                                                                  P14
      Date:2017.02.20
   10   11   12   13   14   15   16   17   18   19   20