Page 11 - 國郁企業股份有限公司 | KUOYUH W.L.Enterprise Co.,Ltd
P. 11

R

             91L Series Thermal Circuit Breaker

             Single Pole Push to Reset


             •Technical data
             •Current rating range  2~20A
             •Input voltage rating  125/250VAC; 50VDC
             •Interrupting Capacity  125/250VAC x 1,000A(UL 1077)
              •Typical life   1,000 operations at 200% overload.
             •Insulation co-ordination  Rated impulse withstand voltage 2.5kV
              •Dielectric Strength  > 1,500VAC/min.
             •Insulation Resistance  >100MOHM (DC 500V)
             •Degree of protection  Terminal area IP00,  operating area IP40
             •Mechanical/Environmental Data
                                                                                                   Amp Rating
             •Operating Ambient Temperature: -10  to +60℃  ℃
              •Termination: 250’’(6.35mm)quick connects or solder terminals
              •Mounting: Various options. See Ordering Information and drawings             KUOYUH  R
                                                                                           91L Series  XXA
                                                                                             R 125/250VAC
             •Compliance with Rohs                                                           50VDC  50/60HZ
                                                                                             TC2/OL1/C1,1KA
                                                                                            . .
                                                                                           T UV  125VAC
              The product accords with the requirement of ROHS( 2011/65/EU)                SUD  50VDC  50/60HZ
              Contacts use Exempted item of RoHS Directive 2010/571/EU 8(a)
             •Compliance with REACH, PAHS, PH1, PH2, PH3
             •Typical applications
                                                                                       * Dimension in mm.
               Tarnsforms, Motors, Battery chargers, Power supplies,
               appliances, extra low voltage systems, machinery.

             •Calibration(at25 )℃
             •100% of Rated Current:      Hold , No Trip
             •150% of Rated Current:      Trip Within 1 Hour.
                                                                   •91L Series 2A~20A Trip Time Curves
              •200% of Rated Current:     5.00-40.0 sec Trip
                                                                     1000%
              •300% of Rated Current:     1.0-5.0 sec Trip           800%                         OverLoad  Trip Time
                                                                                                   600%
                                                                                                       0.25-0.80 sec
                                                                                                       0.30-1.0 sec
                                                                                                   400%
                                                                                                       0.45-2.0 sec
                                                                                                   300%
                                                                                                       1.0-5.0 sec
             •Approval                                               600%                          500%  < 3,600sec(1HR)
                                                                     500%
                                                                                                   200%
                                                                                                       5.00-40.0 sec
                                                                                                   150%
             •Approval & File No.       Rated current     Rated voltage                            100%  Hold, >1 hour
             •CUL UL E155159       2-20A    125/250VAC; 50VDC       Load Current AS Percent of Circuit Breaker Rating  400%
             •TUV SUD B150158611006  5-20A  125VAC; 50VDC            300%
                                                                     200%
                                                                     150%
                                                                     100%
                                                                       0.1     1.0     10      100     1000   10000
                                                                                      TIME IN SECONDS
                                                                                 TRIP CURVES ARE SPECIFIED OF 25°C/77°F
               •Max.Internal Resistance  •Internal connection diagram  •Ambient Temperature Correction Factor
                   2.0-5.0Amp  <0.450 ohms                         Ambient  -10°C  0°C  10°C  25°C  35°C  40°C  50°C  60°C
                                                                   temperature
                   5.1-7.0Amp  <0.150 ohms             Load        Multiplication
                  7.1-10.0Amp  <0.105 ohms                         factor   *1.30  *1.20  *1.10  1.00  *0.94  *0.85  *0.73  *0.68
                 10.1-12.0Amp  <0.075 ohms                        The time/current characteristic curve depends on the ambient temperature prevailing. In order to
                                                                   eliminate nuisance tripping. Please multiply the circuit  breaker current ratings by the derating
                 12.1-15.0Amp  <0.055 ohms
                                                                  factor shown below.
                 15.1-17.0Amp  <0.035 ohms
                                                                  Example : Normal Continuous Current = 10A
                 17.1-20.0Amp  <0.025 ohms                              Ambient Temperature = 45°C
                                                                        Multiplication Factor =  0.85
                                                       Line             Recommended Rating= 10A/0.85=11.8A
      * The specification subject to change without notice. The drawing is for reference only.
      KUOYUH  W.L. Enterprise Co.,Ltd.
      No.17 Kejia 6th Road Douliu City YunLin Hsien 64057  Taiwan R.O.C
                                                                                                      國郁企業股份有限公司
      http//www.kuoyuh.com.tw     sales@kuoyuh.com
                                                                                                      64057 雲林縣斗六市科加六路17號
      Taiwan Tel: 886 5 551 3222  Fax: 886 5 551 3030
      China Tel: 86 769 8366 6388  Fax: 86 769 8366 6362
      Issue:A0                                                                                                  P10
      Date:2017.02.20