R
97 Series Thermal Circuit Breaker
Single Pole; Auto- Reset
•Technical data
•Current rating range 0.8~15A
•Input voltage rating 125/250VAC; 12/24VDC
•Interrupting Capacity 125/250VAC x 200A (UL1077)
•Interrupting capacity Icn 0.8A...1.0A 6x In; AC max 6A
1.1A...1.5A 6x In; AC max 9A
1.6A...15A 8x In; AC max 45A
•Reset time: 200% of rating current within 50 seconds
150% of rating current within 5 minutes
•Dielectric Strength > 1,500VAC/min.
•Insulation Resistance >100MOHM (DC 500V)
•Degree of protection Terminal area IP00; operating area IP30
•Mechanical/Environmental Data
•Operating Ambient Temperature: -10℃ to +60℃
•Termination: 110’’(2.8mm)quick connects or solder terminals ROHS
•Mounting: Various options. See Ordering Information and drawings 97-**** **.*A 125/250VAC **.*A 24VDC
•Compliance with Rohs y z
The product accords with the requirement of ROHS( 2011/65/EU) Line Load
Contacts use Exempted item of RoHS Directive 2010/571/EU 8(a)
•Compliance with REACH, PAHS, PH1, PH2, PH3
•Typical applications
Tarnsforms, Motors, Battery chargers, Power supplies,
appliances, extra low voltage systems, machinery.
•Calibration(at25 )℃
Rated: 0.8~5A •97 Series 0.8-15A Trip Time Curves
•100% of Rated Current: Hold , No Trip
•150% of Rated Current: Trip Within 1 Hour. 1000% Overload % Trip Time 跳脫時間
•200% of Rated Current: 2.0-35 sec Trip 800% 過載百分比 0.8A~5.0A 6A~15A sec
•300% of Rated Current: 0.6-3.5 sec Trip 600% 0.20-1.30 0.25-1.80
600% 400% 0.45-2.20 0.55-3.00
Rated: 6~15A 300% 0.60-3.50 0.85-5.00
•100% of Rated Current: Hold , No Trip 500% 200% 2.0-35.0 3.0-50.0
•135% of Rated Current: Trip Within 1 Hour. 150% Trip in 1 HR 一小時內跳脫
持續,不跳脫.
100%
Hold,No trip
•200% of Rated Current: 3.0-50 sec Trip Circuit Breaker Rating 400%
•300% of Rated Current: 0.85-5 sec Trip Load Current AS Percent of 300%
•Approval
•Approval & File No. Rated current Rated voltage 200%
150%
•CUL UL 0.8-12A 125/250VAC; 12/24VDC 100%
0.1 1 10 100 1000 10000
•Order Guide Trip Curves Are Specified of 25°C/77°F
Time in Seconds
97 - 1 0 0 0 - A •Ambient Temperature Correction Factor
Ambient 0°C 10°C 25°C 35°C 50°C 60°C
Series No Amp Rating Terminal Type temperature -10°C 40°C
Multiplication *1.30 *1.20 *1.10 1.00 *0.94 *0.85 *0.73 *0.68
factor
The time/current characteristic curve depends on the ambient temperature prevailing. In order to
0080=0.8A 0400=4.0A A =P.C.B. 0.5X0.9mm eliminate nuisance tripping. Please multiply the circuit breaker current ratings by the derating
0100=1.0A 0500=5.0A factor shown below.
0125=1.25A 0600=6.0A Example : Normal Continuous Current = 10A
Ambient Temperature = 45°C
0150=1.5A 0700=7.0A Line Load Multiplication Factor = 0.85
0175=1.75A 0800=8.0A Recommended Rating= 10A/0.85=11.8A
0200=2.0A 0900=9.0A 4.80 8.80 Select the Nearest Rating = 12A
•Internal connection diagram
0250=2.5A 1000=10.0A •Max.Internal Resistance •Internal connection diagram
0275=2.75A 1200=12.0A 7.80 0.50 Max resistance V.S Current
rating at 25°c
0300=3.0A 1300=13.0A B =2.8mm S.Q.Terminal Amp rating Max resistance Load
Load
0350=3.5A 1500=15.0A 0.8-1.5 Amp <0.65 ohm
1.6-2.0 Amp <0.15 ohm
Line Load Amp <0.1 ohm
2.1-2.9
3.0-4.0 Amp <0.075 ohm
4.1-6.0 Amp <0.06 ohm
6.1-8.0 Amp <0.05 ohm
L
2.80 0.50 8.1-10.0 Amp <0.045 ohm Line ine
6.40 4.8
11.0-15.0 Amp <0.040 ohm
KUOYUH W.L. Enterprise Co.,Ltd.
KUOYUH W.L. Enterprise Co.,Ltd.
No.17 Kejia 6th Road Douliu City YunLin Hsien 64057 Taiwan R.O.C
http//www.kuoyuh.com.tw sales@kuoyuh.com 國郁企業股份有限公司
64057 雲林縣斗六市科加六路17號
Taiwan Tel: 886 5 551 3222 Fax: 886 5 551 3030
China Tel: 86 769 8366 6388 Fax: 86 769 8366 6362
Issue:A0 P20